Measurement of Power in 3-Phase Circuit

Need help with your homework? Look no further! Our subject experts are ready to effortlessly handle your assignments, so you can finally say goodbye to stress and hello to top grades.

Click or drag files to this area to upload. You can upload up to 3 files.
Get a response in under 15 min

A wattmeter comprises of 2 coils. Those are:

  1. Potential or Pressure coil

This possesses high resistance

  1. Current coil

This possesses low resistance

 

Methods

There are mainly 3 methods with the help of which it is easy to measure power in 3 phase load. Those are:

  1. One wattmeter method
  2. Two wattmeter method
  3. Three wattmeter method

As per this diagram, the current coil is linked to a sequence with the line that carries the current. Across 2 points, a pressure coil is linked where its complete potential difference is measured.

The readings as per wattmeter state the proportionality of resultant of current via its current coil. Now, in accordance withit, we can easily seeitspotential difference across cosine of angle in between current and voltage and its pressure coil.

 

 

Three-Wattmeters Method

 

This figure depicts a star connected load.

This figurine depicts a delta connected load.

As per both these figures, we can clearly see that 3 wattmeters are linked with each other (in 3 phases). These phases are related to load whose connection can be differentiated as either delta connection or as a star connection.

Inside a wattmeter, 2 elements work in a synchronized pattern making its working complete.

  • The pressure coil helps in the measurement of phase voltage of a certain phase.
  • And the current is carried by a current coil that too in a single phase.

These 2 in combination makes sure that measurement of every individual wattmeter relays the amount of power inside one phase. In load, this power in totality is explained via the algebraic sum of readings regarding 3 wattmeters.

Limitations involved in this method

During the application of this method, there are certain difficult aspects that one had to face. Amongst those, 2 are highly important has to be kept in consideration.

  1. Under ordinary circumstance or prospect when it is about delta connected load, practical aspect suggests that phase of load should not be broken.
  2. The usual requirement for connection mainly revolves around neutral point. But when it is about star connected load, in this case, it is generally not possible to achieve that.

There isn’t any specific rule that states that power measurement, the necessary requirement should revolve around 3 wattmeters. For the same purpose, we can use 2 wattmeters too.

 

 

Two-wattmeters method

 

Here are 2 figures.

This figure depicts a star connected load.

This figure depicts a delta connected load.

These figurines are based on 2 wattmeter arrangement. As per this method, in these 2 wattmeters, the insertion of current coils is done in any of the 2 lines. Its potential or pressure coils are connected to third line.

Proof

The provided 3 loads efficiently absorb the sum of instantaneous powers. Its proof can be found by the following equations and explanations.

Let us consider those 3 loads as L3, L2 and L1.

Indication of instantaneous power is relayed via W1 and W2.

In this instance, let us assume the load to be star connected load.

(Instead of this load, one can also assume to opt for delta connected load. And if delta connected load is not available, its easy and best replacement can be equivalent star connected load.)

The most important thing that we have to keep in consideration is the voltage direction when it passes via circuits. This has to be the same when we are trying to establish the readings related to this 2 wattmeter.

Now, with the help of Kirchhoff’s point law, its equation will stand as,

Here, the power which is absorbed by the load depicted by L1 is denoted by P1. Similarly for load L2, the power is depicted by P2 and for load L3, the depiction of power is via P3.

Power in totality that is absorbed is equivalent to the sum of W2 and W1.

This proof can be only considered true when the load is either unbalanced or balanced.

Now in this case, it is a generalized sense that in a star connected load presence of neutral connection is impossible. This is because its arrangement is in a 3 phase and 4 wire format.

Now, if we assume that it has a neutral connection, we have to make sure that there is no flow of neutral current. And for this, the connection has to be exactly balanced. On failure to this, the equation as per Kirchhoff’s point law will be,

iN + iB + iY + iR is equivalent to zero.

This derivation is obtained in accordance with instantaneous readings. Because of the inertia of wattmeter in a moving system is unable to follow swiftly the frequent changes that take place in that cycle. Therefore, the resultant showcases average power. So, the sum of total power regarding W2 and W1 is,

Two wattmeters method related to balanced load

When 2 wattmeters are used, we can find the total power consumption. This power is consumed by balanced load. In case the supposition of inductive load is explained via vector diagram. This assumption is for star connected load which is in a balanced state.

This is the vector figure.

Now, let us assume the entire problem in r.m.s. value. This is an alternate choice over instantaneous values.

As per this value, a star connected system has 3 phase voltages. Let us name those 3 r.m.s. values as EB, EY, ER.

B, Y and R represent the initials of primary colors, blue, yellow and red.

For current, the names for their r.m.s. values are IB, IY, IR.

The assumptions for these currents and voltages are sinusoidal or follow a curved path. The representations for both are highlighted via vectors. As per this, we can see the currents lagging behind phase voltages by ɸ.

For Pressure

In accordance to the above figure, current which passes through the wattmeter, denoted by W1 is equal to IR. So as per vector representation, across the pressure coil of the wattmeter, its potential difference would be,

W1 = ERB

ER – EB = ERB

So,

W1 – ER – EB

With the assistance and by compounding EB and ER in a reverse movement, ERB’s value is obtained. After careful observation it is clearly understood that the phase difference between IR and ERB is equivalent to (30° – ɸ).

So, the reading as per wattmeter W1 will be,

IR x ERB x cos (30° – ɸ) (equation 1)

For Current

Now in similar way, when current passes through wattmeter W2, it is denoted via IY.

So as per vector representation, across the pressure coil of the wattmeter, its potential difference would be,

W2 = EYB

EY – EBI = EYB

So,

W2 = EY – EBI

After compounding EB and EY in a reverse movement, EYB’s value is obtained. . After careful observation it is clearly understood that the phase difference between IY and EYB is equivalent to (30° + ɸ).

So, the reading as per wattmeter W2 will be,

IY x EYB x cos (30° + ɸ) (equation 2)

Since the load is found to be in a balanced position, line current will be,

IL = IY = IR

Similarly, for line voltage it will be,

EL = EYB = ERB

Therefore the equation will be,

Its total power will be,

P = W2 + W1

So, for 2 wattmeters, the sum of their readings that would relay the total power consumption with regards to 3 phase load. It is important that we must consider the fact that we have assumed the phase order of RYB for establishing the readings for this 2 wattmeter. Also we need to consider the fact that if this sequence or order changes or reverses, its resultant will also get reversed.

Variations in case of wattmeter readings

The above factors highlights lagging power factor from whom the equations will be,

It is evident from the equations of wattmeters that these separate readings are dependent on both its power factor and load.

There are 4 cases that will help us understand this variation.

In the first case,

#1

When the value of ɸ is equal to 0, it can be stated that the load is resistive. As per this, it can be also assumed that the value of power factor is considered to be unity.

So, it can be stated in equational form that,

W2 = W1 = IL x EL x cos 30°

According to this, it is evident that readings for every wattmeter will be both opposite and equal. This reading is an up-scale reading.

Now for the second case,

#2

When the value of ɸ is equal to 60°, it can be stated that the load is lagging. As per this, it can be also assumed that the value of power factor is considered to be 0.5.

So, it can be stated in equational form that,

W2 = IL x EL x cos 60° + 30°

Therefore, W2 = 0

 

 

 

Two-wattmeters method

 

 

Here are 2 figures.

This figure depicts a star connected load.

This figure depicts a delta connected load.

These figurines are based on 2 wattmeter arrangement. As per this method, in these 2 wattmeters, the insertion of current coils is done in any of the 2 lines. Its potential or pressure coils are connected to third line.

Proof

The provided 3 loads efficiently absorb the sum of instantaneous powers. Its proof can be found by the following equations and explanations.

Let us consider those 3 loads as L3, L2, and L1.

An indication of instantaneous power is relayed via W1 and W2.

In this instance, let us assume the load to be star connected load.

(Instead of this load, one can also assume to opt for delta connected load. And if delta connected load is not available, its easy and best replacement can be equivalent star connected load.)

The most important thing that we have to keep in consideration is the voltage direction when it passes via circuits. This has to be the same when we are trying to establish the readings related to this 2 wattmeter.

Now, with the help of Kirchhoff’s point law, its equation will stand as,

Here, the power which is absorbed by the load depicted by L1 is denoted by P1. Similarly, for load L2, the power is depicted by P2, and for load L3, the depiction of power is via P3.

Power in totality that is absorbed is equivalent to the sum of W2 and W1.

This proof can be only considered true when the load is either unbalanced or balanced.

Now, in this case, it is a generalized sense that in a star connected load presence of a neutral connection is impossible. This is because its arrangement is in a 3 phase and 4 wire format.

Now, if we assume that it has a neutral connection, we have to make sure that there is no flow of neutral current. And for this, the connection has to be exactly balanced. On failure to this, the equation as per Kirchhoff’s point law will be,

iN + iB + iY + iR is equivalent to zero.

This derivation is obtained in accordance with instantaneous readings. Because of the inertia of wattmeter in a moving system, it is unable to follow swiftly the frequent changes that take place in that cycle. Therefore, the resultant showcases average power. So, the sum of total power regarding W2 and W1 is,

Two wattmeters method related to balanced load

When 2 wattmeters are used, we can find the total power consumption. This power is consumed by balanced load. In case the supposition of inductive load is explained via vector diagram. This assumption is for star connected load which is in a balanced state.

This is the vector figure.

Now, let us assume the entire problem in r.m.s. value. This is an alternate choice over instantaneous values.

As per this value, a star connected system has 3 phase voltages. Let us name that 3 r.m.s. values as EB, EY, ER.

B, Y, and R represent the initials of primary colors, blue, yellow and red.

For current, the names for their r.m.s. values are IB, IY, IR.

The assumptions for these currents and voltages are sinusoidal or follow a curved path. The representations for both are highlighted via vectors. As per this, we can see the currents lagging behind phase voltages by ɸ.

For Pressure

In accordance with the above figure, current which passes through the wattmeter, denoted by W1 is equal to IR. So as per vector representation, across the pressure coil of the wattmeter, its potential difference would be,

W1 = ERB

ER – EB = ERB

So,

W1 – ER – EB

With the assistance and by compounding EB and ER in a reverse movement, ERB’s value is obtained. After careful observation, it is clearly understood that the phase difference between IR and ERB is equivalent to (30° – ɸ).

So, the reading as per wattmeter W1 will be,

IR x ERB x cos (30° – ɸ) (equation 1)

For Current

Now in a similar way, when current passes through wattmeter W2, it is denoted via IY.

So as per vector representation, across the pressure coil of the wattmeter, its potential difference would be,

W2 = EYB

EY – EBI = EYB

So,

W2 = EY – EBI

After compounding EB and EY in a reverse movement, EYB’s value is obtained. After careful observation, it is clearly understood that the phase difference between IY and EYB is equivalent to (30° + ɸ).

So, the reading as per wattmeter W2 will be,

IY x EYB x cos (30° + ɸ) (equation 2)

Since the load is found to be in a balanced position, line current will be,

IL = IY = IR

Similarly, for line voltage, it will be,

EL = EYB = ERB

Therefore the equation will be,

Its total power will be,

P = W2 + W1

So, for 2 wattmeters, the sum of their readings that would relay the total power consumption with regards to 3 phase load. It is important that we must consider the fact that we have assumed the phase order of RYB for establishing the readings for this 2 wattmeter. Also, we need to consider the fact that if this sequence or order changes or reverses, its resultant will also get reversed.

Variations in case of wattmeter readings

The above factors highlights lagging power factor from whom the equations will be,

It is evident from the equations of wattmeters that these separate readings are dependent on both its power factor and load.

There are 4 cases that will help us understand this variation.

In the first case,

#1

When the value of ɸ is equal to 0, it can be stated that the load is resistive. As per this, it can also be assumed that the value of power factor is considered to be unity.

So, it can be stated in equational form that,

W2 = W1 = IL x EL x cos 30°

According to this, it is evident that readings for every wattmeter will be both opposite and equal. This reading is an up-scale reading.

Now for the second case,

#2

When the value of ɸ is equal to 60°, it can be stated that the load is lagging. As per this, it can also be assumed that the value of power factor is considered to be 0.5.

So, it can be stated in equational form that,

W2 = IL x EL x cos 60° + 30°

Therefore, W2 = 0

So, the measurement of power is done via W1.

#3

As per this case, we can see that W1’s reading is positive whereas its counterpart, W2’s reading is just the opposite. And even for leading p.f., the required condition is just reversed. The reason for W1 to give a reading that is reversed or negative is due to its phase angle which is more than 90° between voltage and current.

W2 – W1 = total power

Here, the reading for W2 is termed as backward or down scale. And in order to acquire its readings, it is highly essential that either its current coil or its pressure coil is reversed. This will give its reading in negative.

#4

In accordance to this 2 readings, both of their magnitudes are equivalent, but their signs are opposite.

Therefore, sum of W1 and W2 is zero.

The consideration and sign for lagging angles are taken as positive. But when power factor with respect to a wattmeter changes, its readings will be,

Therefore, via angles related to 2 wattmeter leads to readings which are interchanged. So, the equations when power is leading will be,

Power factor in case the load is balanced

In case the balanced load has a lagging power factor, and it is clearly showcased that current and voltage are sinusoidal, its equation will be,

After the value of tan ɸ is obtained, with the help of trigonometrical tables the value of cos ɸ can also be calculated.

One of the most important while taking this reading is the consideration for W2, which is obtained by reversing the significant pressure coil. So now, the equation will be,

The expression for power factor can also be represented in ratio format related to the readings of 2 wattmeters.

Watt ratio curve

Plotting of curve between cos ɸ and α is known as watt ratio curve. This curve will look like,

With two wattmeters reactive volt amperes

We are already aware that,

As per this, tangent of angle of lag which is between phase voltages and phases current of a circuit is equivalent to ratio of reactive power over true power. Therefore, the difference of reactive power’s reading with respect to 2 wattmeters is utilized for power measurement of 3 phase circuit.

Mathematical proof with figure

 

One-wattmeter method

In accordance with this method, in any certain one line, the current coil is linked, and its connection for pressure coil is alternately placed between the other 2 lines. Inside a balanced load, important 2 readings which are acquired are based on wattmeter method.

 

Links of Previous Main Topic:-

Links of Next Electrical Engineering Topics:-

Homework Blues?

Get expert help with homework for all subjects.

  • NPlagiarism-free work
  • NHonest Pricing
  • NMoney-back guarantee

Latest Reviews

Solved Sample Works

Accounting Homework

Corporate Accounting Sample

Biology Homework

Genetics Assignment Sample

Essay Writing Help

Business Plan Sample

Homework Help FAQs

Our Answers to Your Questions

How do I submit my homework?
K
L

Getting homework help is very simple with us. Students can either send us the homework via email or they can upload it to our online form here. For a quicker response, You can also chat with us at WhatsApp and submit homework directly. You are sure to get a response from our side within 10 minutes.

How much will my homework cost?
K
L

The cost of paying someone to do your homework varies depending on the service and the type of assignment. We have listed our standard pricing plans for popularly used writing services. For other kind of assignments, You can get a free instant quote from us using our online form.

We also accept partial payment to start working on your assignment help. You can pay the remaining amount when your task gets completed. No pressure of up-front payment. No hidden order costs.

Can I receive help with my homework anytime?
K
L

Yes, you can receive help with your homework anytime with us. Our online homework help services are available 24/7, allowing you to receive assistance with your homework anytime, anywhere.

For urgent homework requests, reach out to us through our LiveChat or WhatsApp channels and one of our friendly support agents will assist you in finding the right expert for your online homework help request immediately. With our services, you can rely on 24/7 availability and meeting deadlines.

Are online homework websites budget-friendly for students like me?
K
L

Yes, Our Online Homework Help websites are an affordable solution for you as a student. Compared to traditional tutoring services, MyHomeworkHelp prices their homework help services honestly and within the budget of college students. This makes it easier for you to receive assistance with your homework without breaking the bank.

What is your plagiarism-free policy?
K
L

At myhomeworkhelp, we take plagiarism very seriously and ensure that all solutions provided by our tutors are original and authentic. Our tutors are trained to provide custom-made solutions, tailored specifically to meet the requirements of each student. We do not provide pre-written papers. All our homeswork solutions are made from scratch, guaranteeing 100% orignal homework answers.

Additionally, we have strict plagiarism-detection tools in place to check all submissions for authenticity.

Is using an Online Homework Help Service cheating?
K
L

Using online homework help services is not equivalent to cheating. Our services are intended to support students with their homework and provide them with the resources they need to succeed academically. With the help of our online homework help services, students can receive immediate assistance with their homework from any location, at any time.

At myhomeworkhelp, we are committed to promoting academic integrity. Our tutors provide solutions that serve as guides for drafting your own work. It is not acceptable to submit someone else's work as your own, as this constitutes academic plagiarism.

Can I chat with my tutor?
K
L

Using our secure chat board, you can now chat directly with your assigned tutor. The chats are encrypted both ways to secure your privacy. This makes your contact with the tutor directly & confidentially, so you can better explain any requirements or changes if needed or just need updates.

You can't contact the experts outside of chat board platform. Sharing any personal information, including but not limited to contact information, goes against our Terms and Conditions and therefore may result in permanently blocking you from the platform. We take any personal data very seriously and we do it for the safety of our users.

Know more about chat board here.

What is your money-back guarantee policy?
K
L

It’s worth noting that our online homework help service rarely leads to disappointment among students. Our expert tutors, along with our support and quality assurance team, are dedicated to providing the best possible experience for our customers. However, if for any reason a student is unsatisfied with their homework help solution, we offer unlimited revisions until they are fully satisfied.

In the rare event that a student remains unsatisfied even after revisions, we offer a money-back guarantee. We want all of our students to feel confident and secure when they turn to us for assistance with their homework, and this guarantee is just one way that we demonstrate our commitment to providing the best possible service. If you have any concerns about our services or the quality of the work you receive, please contact us for support.

What is the expertise of the tutor assigned to do my homework?
K
L

At myhomeworkhelp, we take pride in our team of qualified and experienced tutors. All of our tutors undergo a rigorous selection process and are required to have a minimum of a master's degree in their respective fields. Additionally, they must pass a series of tests to demonstrate their proficiency and ability to deliver quality work. We believe in transparency and providing our clients with the best possible service. You can be confident in the expertise of the tutor assigned to do your homework.

What about privacy & confidentiality?
K
L

Using My Homework Help is absolutely safe. We care about your security, therefore we encrypt all personal data to make every user feel safe while using our services and we don’t share any personal information with any third parties without your permission. Your credit card information is not stored anywhere at My Homework Help, and use of PayPal relies on their secure payment networks. Your identity, payment and homework are in safe hands. You can always be certain of getting professional help and remaining anonymous, while using My Homework Help.