my homework help logo

Measurement of Power in 3-Phase Circuit

Need a hand with your homework? Get expert help now and smash those grades! 💯 Submit your assignment today!

100% human expertise, no AI. 🤖

Checkmark Expert Tutors Checkmark Affordable Pricing Checkmark On-Time Delivery
Become one of the 50K+ happy customers!
Please enable JavaScript in your browser to complete this form.
Helps us find best expert for you
When is it due?

A wattmeter comprises of 2 coils. Those are:

  1. Potential or Pressure coil

This possesses high resistance

  1. Current coil

This possesses low resistance

 

Methods

There are mainly 3 methods with the help of which it is easy to measure power in 3 phase load. Those are:

  1. One wattmeter method
  2. Two wattmeter method
  3. Three wattmeter method

As per this diagram, the current coil is linked to a sequence with the line that carries the current. Across 2 points, a pressure coil is linked where its complete potential difference is measured.

The readings as per wattmeter state the proportionality of resultant of current via its current coil. Now, in accordance withit, we can easily seeitspotential difference across cosine of angle in between current and voltage and its pressure coil.

 

 

Three-Wattmeters Method

 

This figure depicts a star connected load.

This figurine depicts a delta connected load.

As per both these figures, we can clearly see that 3 wattmeters are linked with each other (in 3 phases). These phases are related to load whose connection can be differentiated as either delta connection or as a star connection.

Inside a wattmeter, 2 elements work in a synchronized pattern making its working complete.

  • The pressure coil helps in the measurement of phase voltage of a certain phase.
  • And the current is carried by a current coil that too in a single phase.

These 2 in combination makes sure that measurement of every individual wattmeter relays the amount of power inside one phase. In load, this power in totality is explained via the algebraic sum of readings regarding 3 wattmeters.

Limitations involved in this method

During the application of this method, there are certain difficult aspects that one had to face. Amongst those, 2 are highly important has to be kept in consideration.

  1. Under ordinary circumstance or prospect when it is about delta connected load, practical aspect suggests that phase of load should not be broken.
  2. The usual requirement for connection mainly revolves around neutral point. But when it is about star connected load, in this case, it is generally not possible to achieve that.

There isn’t any specific rule that states that power measurement, the necessary requirement should revolve around 3 wattmeters. For the same purpose, we can use 2 wattmeters too.

 

 

Two-wattmeters method

 

Here are 2 figures.

This figure depicts a star connected load.

This figure depicts a delta connected load.

These figurines are based on 2 wattmeter arrangement. As per this method, in these 2 wattmeters, the insertion of current coils is done in any of the 2 lines. Its potential or pressure coils are connected to third line.

Proof

The provided 3 loads efficiently absorb the sum of instantaneous powers. Its proof can be found by the following equations and explanations.

Let us consider those 3 loads as L3, L2 and L1.

Indication of instantaneous power is relayed via W1 and W2.

In this instance, let us assume the load to be star connected load.

(Instead of this load, one can also assume to opt for delta connected load. And if delta connected load is not available, its easy and best replacement can be equivalent star connected load.)

The most important thing that we have to keep in consideration is the voltage direction when it passes via circuits. This has to be the same when we are trying to establish the readings related to this 2 wattmeter.

Now, with the help of Kirchhoff’s point law, its equation will stand as,

Here, the power which is absorbed by the load depicted by L1 is denoted by P1. Similarly for load L2, the power is depicted by P2 and for load L3, the depiction of power is via P3.

Power in totality that is absorbed is equivalent to the sum of W2 and W1.

This proof can be only considered true when the load is either unbalanced or balanced.

Now in this case, it is a generalized sense that in a star connected load presence of neutral connection is impossible. This is because its arrangement is in a 3 phase and 4 wire format.

Now, if we assume that it has a neutral connection, we have to make sure that there is no flow of neutral current. And for this, the connection has to be exactly balanced. On failure to this, the equation as per Kirchhoff’s point law will be,

iN + iB + iY + iR is equivalent to zero.

This derivation is obtained in accordance with instantaneous readings. Because of the inertia of wattmeter in a moving system is unable to follow swiftly the frequent changes that take place in that cycle. Therefore, the resultant showcases average power. So, the sum of total power regarding W2 and W1 is,

Two wattmeters method related to balanced load

When 2 wattmeters are used, we can find the total power consumption. This power is consumed by balanced load. In case the supposition of inductive load is explained via vector diagram. This assumption is for star connected load which is in a balanced state.

This is the vector figure.

Now, let us assume the entire problem in r.m.s. value. This is an alternate choice over instantaneous values.

As per this value, a star connected system has 3 phase voltages. Let us name those 3 r.m.s. values as EB, EY, ER.

B, Y and R represent the initials of primary colors, blue, yellow and red.

For current, the names for their r.m.s. values are IB, IY, IR.

The assumptions for these currents and voltages are sinusoidal or follow a curved path. The representations for both are highlighted via vectors. As per this, we can see the currents lagging behind phase voltages by ɸ.

For Pressure

In accordance to the above figure, current which passes through the wattmeter, denoted by W1 is equal to IR. So as per vector representation, across the pressure coil of the wattmeter, its potential difference would be,

W1 = ERB

ER – EB = ERB

So,

W1 – ER – EB

With the assistance and by compounding EB and ER in a reverse movement, ERB’s value is obtained. After careful observation it is clearly understood that the phase difference between IR and ERB is equivalent to (30° – ɸ).

So, the reading as per wattmeter W1 will be,

IR x ERB x cos (30° – ɸ) (equation 1)

For Current

Now in similar way, when current passes through wattmeter W2, it is denoted via IY.

So as per vector representation, across the pressure coil of the wattmeter, its potential difference would be,

W2 = EYB

EY – EBI = EYB

So,

W2 = EY – EBI

After compounding EB and EY in a reverse movement, EYB’s value is obtained. . After careful observation it is clearly understood that the phase difference between IY and EYB is equivalent to (30° + ɸ).

So, the reading as per wattmeter W2 will be,

IY x EYB x cos (30° + ɸ) (equation 2)

Since the load is found to be in a balanced position, line current will be,

IL = IY = IR

Similarly, for line voltage it will be,

EL = EYB = ERB

Therefore the equation will be,

Its total power will be,

P = W2 + W1

So, for 2 wattmeters, the sum of their readings that would relay the total power consumption with regards to 3 phase load. It is important that we must consider the fact that we have assumed the phase order of RYB for establishing the readings for this 2 wattmeter. Also we need to consider the fact that if this sequence or order changes or reverses, its resultant will also get reversed.

Variations in case of wattmeter readings

The above factors highlights lagging power factor from whom the equations will be,

It is evident from the equations of wattmeters that these separate readings are dependent on both its power factor and load.

There are 4 cases that will help us understand this variation.

In the first case,

#1

When the value of ɸ is equal to 0, it can be stated that the load is resistive. As per this, it can be also assumed that the value of power factor is considered to be unity.

So, it can be stated in equational form that,

W2 = W1 = IL x EL x cos 30°

According to this, it is evident that readings for every wattmeter will be both opposite and equal. This reading is an up-scale reading.

Now for the second case,

#2

When the value of ɸ is equal to 60°, it can be stated that the load is lagging. As per this, it can be also assumed that the value of power factor is considered to be 0.5.

So, it can be stated in equational form that,

W2 = IL x EL x cos 60° + 30°

Therefore, W2 = 0

 

 

 

Two-wattmeters method

 

 

Here are 2 figures.

This figure depicts a star connected load.

This figure depicts a delta connected load.

These figurines are based on 2 wattmeter arrangement. As per this method, in these 2 wattmeters, the insertion of current coils is done in any of the 2 lines. Its potential or pressure coils are connected to third line.

Proof

The provided 3 loads efficiently absorb the sum of instantaneous powers. Its proof can be found by the following equations and explanations.

Let us consider those 3 loads as L3, L2, and L1.

An indication of instantaneous power is relayed via W1 and W2.

In this instance, let us assume the load to be star connected load.

(Instead of this load, one can also assume to opt for delta connected load. And if delta connected load is not available, its easy and best replacement can be equivalent star connected load.)

The most important thing that we have to keep in consideration is the voltage direction when it passes via circuits. This has to be the same when we are trying to establish the readings related to this 2 wattmeter.

Now, with the help of Kirchhoff’s point law, its equation will stand as,

Here, the power which is absorbed by the load depicted by L1 is denoted by P1. Similarly, for load L2, the power is depicted by P2, and for load L3, the depiction of power is via P3.

Power in totality that is absorbed is equivalent to the sum of W2 and W1.

This proof can be only considered true when the load is either unbalanced or balanced.

Now, in this case, it is a generalized sense that in a star connected load presence of a neutral connection is impossible. This is because its arrangement is in a 3 phase and 4 wire format.

Now, if we assume that it has a neutral connection, we have to make sure that there is no flow of neutral current. And for this, the connection has to be exactly balanced. On failure to this, the equation as per Kirchhoff’s point law will be,

iN + iB + iY + iR is equivalent to zero.

This derivation is obtained in accordance with instantaneous readings. Because of the inertia of wattmeter in a moving system, it is unable to follow swiftly the frequent changes that take place in that cycle. Therefore, the resultant showcases average power. So, the sum of total power regarding W2 and W1 is,

Two wattmeters method related to balanced load

When 2 wattmeters are used, we can find the total power consumption. This power is consumed by balanced load. In case the supposition of inductive load is explained via vector diagram. This assumption is for star connected load which is in a balanced state.

This is the vector figure.

Now, let us assume the entire problem in r.m.s. value. This is an alternate choice over instantaneous values.

As per this value, a star connected system has 3 phase voltages. Let us name that 3 r.m.s. values as EB, EY, ER.

B, Y, and R represent the initials of primary colors, blue, yellow and red.

For current, the names for their r.m.s. values are IB, IY, IR.

The assumptions for these currents and voltages are sinusoidal or follow a curved path. The representations for both are highlighted via vectors. As per this, we can see the currents lagging behind phase voltages by ɸ.

For Pressure

In accordance with the above figure, current which passes through the wattmeter, denoted by W1 is equal to IR. So as per vector representation, across the pressure coil of the wattmeter, its potential difference would be,

W1 = ERB

ER – EB = ERB

So,

W1 – ER – EB

With the assistance and by compounding EB and ER in a reverse movement, ERB’s value is obtained. After careful observation, it is clearly understood that the phase difference between IR and ERB is equivalent to (30° – ɸ).

So, the reading as per wattmeter W1 will be,

IR x ERB x cos (30° – ɸ) (equation 1)

For Current

Now in a similar way, when current passes through wattmeter W2, it is denoted via IY.

So as per vector representation, across the pressure coil of the wattmeter, its potential difference would be,

W2 = EYB

EY – EBI = EYB

So,

W2 = EY – EBI

After compounding EB and EY in a reverse movement, EYB’s value is obtained. After careful observation, it is clearly understood that the phase difference between IY and EYB is equivalent to (30° + ɸ).

So, the reading as per wattmeter W2 will be,

IY x EYB x cos (30° + ɸ) (equation 2)

Since the load is found to be in a balanced position, line current will be,

IL = IY = IR

Similarly, for line voltage, it will be,

EL = EYB = ERB

Therefore the equation will be,

Its total power will be,

P = W2 + W1

So, for 2 wattmeters, the sum of their readings that would relay the total power consumption with regards to 3 phase load. It is important that we must consider the fact that we have assumed the phase order of RYB for establishing the readings for this 2 wattmeter. Also, we need to consider the fact that if this sequence or order changes or reverses, its resultant will also get reversed.

Variations in case of wattmeter readings

The above factors highlights lagging power factor from whom the equations will be,

It is evident from the equations of wattmeters that these separate readings are dependent on both its power factor and load.

There are 4 cases that will help us understand this variation.

In the first case,

#1

When the value of ɸ is equal to 0, it can be stated that the load is resistive. As per this, it can also be assumed that the value of power factor is considered to be unity.

So, it can be stated in equational form that,

W2 = W1 = IL x EL x cos 30°

According to this, it is evident that readings for every wattmeter will be both opposite and equal. This reading is an up-scale reading.

Now for the second case,

#2

When the value of ɸ is equal to 60°, it can be stated that the load is lagging. As per this, it can also be assumed that the value of power factor is considered to be 0.5.

So, it can be stated in equational form that,

W2 = IL x EL x cos 60° + 30°

Therefore, W2 = 0

So, the measurement of power is done via W1.

#3

As per this case, we can see that W1’s reading is positive whereas its counterpart, W2’s reading is just the opposite. And even for leading p.f., the required condition is just reversed. The reason for W1 to give a reading that is reversed or negative is due to its phase angle which is more than 90° between voltage and current.

W2 – W1 = total power

Here, the reading for W2 is termed as backward or down scale. And in order to acquire its readings, it is highly essential that either its current coil or its pressure coil is reversed. This will give its reading in negative.

#4

In accordance to this 2 readings, both of their magnitudes are equivalent, but their signs are opposite.

Therefore, sum of W1 and W2 is zero.

The consideration and sign for lagging angles are taken as positive. But when power factor with respect to a wattmeter changes, its readings will be,

Therefore, via angles related to 2 wattmeter leads to readings which are interchanged. So, the equations when power is leading will be,

Power factor in case the load is balanced

In case the balanced load has a lagging power factor, and it is clearly showcased that current and voltage are sinusoidal, its equation will be,

After the value of tan ɸ is obtained, with the help of trigonometrical tables the value of cos ɸ can also be calculated.

One of the most important while taking this reading is the consideration for W2, which is obtained by reversing the significant pressure coil. So now, the equation will be,

The expression for power factor can also be represented in ratio format related to the readings of 2 wattmeters.

Watt ratio curve

Plotting of curve between cos ɸ and α is known as watt ratio curve. This curve will look like,

With two wattmeters reactive volt amperes

We are already aware that,

As per this, tangent of angle of lag which is between phase voltages and phases current of a circuit is equivalent to ratio of reactive power over true power. Therefore, the difference of reactive power’s reading with respect to 2 wattmeters is utilized for power measurement of 3 phase circuit.

Mathematical proof with figure

 

One-wattmeter method

In accordance with this method, in any certain one line, the current coil is linked, and its connection for pressure coil is alternately placed between the other 2 lines. Inside a balanced load, important 2 readings which are acquired are based on wattmeter method.

 

Links of Previous Main Topic:-

Links of Next Electrical Engineering Topics:-

Your Price: $15.00 $13.99 🔥

Pricing may change based on requirements

Get Homework Help In

Maths and Statistics

Science

Humanities & Arts

l

Essay Writing

How Our Homework Service Works

FAQ number 1

Share your requirements

FAQ number 2

Make secure payment

FAQ number 3

Get homework answers

FAQ - Our Homework Help Services

We have put together some commonly asked questions.

K
L

Is there a website that can do my homework?

Yes, if you are looking for such a site, MyHomeworkHelp is one of the leading homework help websites that can do your homework and assist with various academic needs. Here's all you need to know about our team and how they provide flawless homework help.

If you find yourself thinking, "I need to pay someone to do my homework," our team is ready to assist. It's common for students to seek help with their homework, and our experts are prepared to provide personalized support tailored to your needs.

You can visit www.myhomeworkhelp.com to get all types of homework-related help from our experts.

K
L

What is the best homework help website?

The best homework help website enhances students' experience of getting homework assistance from experts. MyHomeworkHelp, recognized as one of the best online homework help platforms, serves as both a guide and a solution provider for students. We've been rocking the homework help scene since 2012, assisting over 20k students, and we must be doing something right because more than 70% of them keep coming back for more. Whether you need help understanding concepts, completing assignments, or getting your homework done, MyHomeworkHelp is here to support your academic journey as the best college homework website.

K
L

How can I get help with my homework?

1. Tell us your homework details

To get started with online homework help, simply choose the type of homework assistance you need. When filling out the order form, make sure to provide detailed instructions, including the deadline, number of pages, grading rubric, and any other relevant information.

2. Confirm your order

Review the details of your homework order and proceed to make a secure payment using VISA, Mastercard, or PayPal. Once the payment is processed, our experts will begin working on your homework immediately.

3. Receive your order

The completed homework will be delivered directly to your email. This ensures that students receive their homework assistance on time and can meet their academic requirements without stress.

K
L

Do you guarantee plagiarism-free homework answers?

We take academic integrity very seriously and understand the importance of providing homework answers free of plagiarism. Our tutors are committed to delivering original and unique content for every assignment. Here are the steps we take to ensure your homework is plagiarism-free:

  1. Original Work: Each assignment is completed from scratch based on your specific requirements and guidelines.
  2. Expert Tutors: Our tutors are highly qualified and experienced in their respective fields, ensuring the work they produce is both original and high-quality.
  3. Plagiarism Detection: We use advanced plagiarism detection software to scan every assignment before delivery. This ensures that the content is unique and free of any copied material.
  4. No AI Usage: We guarantee that all work is 100% human-crafted expertise, with no AI-generated content involved. This ensures the authenticity and quality of the work provided.
  5. Quality Assurance: Our quality assurance team reviews each assignment for originality and adherence to academic standards before it is sent to you.

By following these stringent measures, we guarantee that the homework answers you receive are completely free of plagiarism and AI involvement. You can trust us to provide you with original and high-quality academic assistance.

For more information on our guarantees, please visit our guarantees page.

K
L

Is your homework service confidential?

Absolutely! Confidentiality is one of the basic guarantees of our service at MyHomeworkHelp.com.

When our customers make their homework orders, they know their information remains 100% confidential.

Even your homework writer will not be provided with your personal details. So, when you hire a professional homework helper on our website, rest assured that your information will remain private and safe.

For a comprehensive understanding of how we protect your privacy, please refer to our Privacy Policy.

K
L

How much do I need to pay to get my homework done?

We do not have monthly fees or minimum payments for our services. Each homework assignment is quoted a unique price, based on the tutor’s estimate of the time required to complete your work. There are no obligations, and you are free to discuss the price quote with the tutor.

When you decide to pay someone to do my homework, our pricing starts at $13.99 per page. The final pricing depends on various factors including the page count, deadline, nature of the task, and the homework writer’s level of expertise.

We offer flexible payment options, allowing you to make a partial payment to start working on your assignment and pay the remaining amount upon completion. This ensures no pressure of up-front payment and no hidden order costs.

Our dynamic pricing model takes into account the type of assignment, its urgency, and the complexity of the task. For instance, shorter deadlines and more complex assignments may increase the price. You can get an instant quote by selecting your assignment type, deadline, and page count on our website.

Get the help with your homework at competitive rates, tailored to your specific needs and deadlines. For more detailed information on pricing, please visit our pricing page.

K
L

Who are the experts who will help me with my homework?

We work with subject experts from all over the world. We hire them with the help of complex tests in the disciplines of their expertise. We also verify the IDs and academic transcripts of our homework writers to be sure that our experts have a bachelor's or master’s or a PhD degree. This is how we can be sure of the proficiency of our panel of experts who will help you with your homework. Here's all you need to know about our team and how they provide flawless homework help.

  1. Our team comprises top-tier homework helpers who excel in addressing and resolving questions on various topics. Each tutor effectively utilizes their expertise to concentrate on the core subject matter and thoroughly analyze it.
  2. Our professional tutors specifically craft each assignment tailored to students' requirements, including preferred formats, citation styles, and essential elements.
  3. Whether it’s coursework, dissertations, essays, or case studies, our platform guarantees timely college homework help across a wide range of academic papers. Don’t hesitate any longer; connect with our tutors when you seek help with your homework for perfect assignment solutions and improved grades.

K
L

Can I chat with my homework helper for updates?

Yes, you can certainly chat with your homework helper on our secure chatboard platform. MyHomeworkHelp.com provides a direct communication channel between you and your assigned expert (while maintaining privacy). This feature allows you to ask questions, clarify instructions, and provide additional information about your homework order to ensure that the help you receive is tailored to your specific needs.

You'll be notified by email whenever there are new messages for you, but we advise regularly checking your personal page to ensure no critical updates from your writer are overlooked.

Should you have an urgent matter to address, do not hesitate to contact the support team for assistance. This system ensures that students can stay updated on their homework paper progress and maintain clear communication with their experts.

K
L

What makes you the best homework helper?

MyHomeworkHelp is ranked as one of the best online homework helpers, providing exceptional support to students. We've been excelling in the homework assistance arena since 2012, assisting over 200k students, and consistently achieving high satisfaction rates, with more than 70% of our students returning for additional help. But do not take our word for it! See our independent reviews on google, facebook, sitejabber, and on Trustpilot. For all collated reviews, see here

We ensure our prices remain competitive and offer attractive discounts to make our services accessible. Our commitment to delivering plagiarism-free solutions guarantees the integrity and originality of your assignments. These attributes, combined with our dedication to personalized support and timely delivery, establish MyHomeworkHelp as the premier homework helper for all your academic needs.

K
L

How will I receive my homework order?

You'll receive the initial version of your paper as a secure, non-editable PDF within your specified deadline. This allows you to review the content and decide if any revisions or edits are required. Our homework service will refine the homework paper based on your feedback.

Should the document meet your expectations and not require any changes, you can simply approve the order and access the editable Word .doc file.